型號 | 觸點形式 | 額定電壓 | 設定值 | |
HOVS-58VAC-2H | 2常開 | AC:58V | 50%~105%額定電壓 | |
HOVS-100VAC-2H | 2常開 | AC:100V | 50%~105%額定電壓 | |
HOVS-110VAC-2H | 2常開 | AC:110V | 50%~105%額定電壓 | |
HOVS-220VAC-2H | 2常開 | AC:220V | 50%~105%額定電壓 | |
HOVS-58VAC-4H | 4常開 | AC:58V | 50%~105%額定電壓 | |
HOVS-100VAC-4H | 4常開 | AC:100V | 50%~105%額定電壓 | |
HOVS-110VAC-4H | 4常開 | AC:110V | 50%~105%額定電壓 | |
HOVS-220VAC-4H | 4常開 | AC:220V | 50%~105%額定電壓 | |
HOVS-58VAC-2H2D | 2常開2常閉 | AC:58V | 50%~105%額定電壓 | |
HOVS-100VAC-2H2D | 2常開2常閉 | AC:100V | 50%~105%額定電壓 | |
HOVS-110VAC-2H2D | 2常開2常閉 | AC:110V | 50%~105%額定電壓 | |
HOVS-220VAC-2H2D | 2常開2常閉 | AC:220V | 50%~105%額定電壓 | |
HOVT-58VAC-2H | 2常開 | AC:58V | 50%~105%額定電壓 | |
HOVT-100VAC-2H | 2常開 | AC:100V | 50%~105%額定電壓 | |
HOVT-110VAC-2H | 2常開 | AC:110V | 50%~105%額定電壓 | |
HOVT-220VAC-2H | 2常開 | AC:220V | 50%~105%額定電壓 | |
HOVT-58VAC-4H | 4常開 | AC:58V | 50%~105%額定電壓 | |
HOVT-100VAC-4H | 4常開 | AC:100V | 50%~105%額定電壓 | |
HOVT-110VAC-4H | 4常開 | AC:110V | 50%~105%額定電壓 | |
HOVT-220VAC-4H | 4常開 | AC:220V | 50%~105%額定電壓 | |
HOVT-58VAC-2H2D | 2常開2常閉 | AC:58V | 50%~105%額定電壓 | |
HOVT-100VAC-2H2D | 2常開2常閉 | AC:100V | 50%~105%額定電壓 | |
HOVT-110VAC-2H2D | 2常開2常閉 | AC:110V | 50%~105%額定電壓 | |
HOVT-220VAC-2H2D | 2常開2常閉 | AC:220V | 50%~105%額定電壓 |
額定參數 | |
額定電壓 | AC58V、100V、110V、220V |
電壓范圍 | 40%~110%額定電壓 |
設定值 | 50%~105% |
動作時間 | 1.2倍整定值≤35ms、1.2倍整定值≤20ms |
返回時間 | ≤35ms |
功耗 | <5W |
絕緣性能 | |
絕緣電阻 | 繼電器外殼與外露帶電端子之間用開路電壓500V的兆歐表測量,絕緣電阻不小于10MΩ |
絕緣耐壓 | 繼電器外殼與外露帶電端子之間能耐受2KV(有效值)50Hz試驗電壓,歷時1分鐘,無擊穿或閃絡現(xiàn)象 |
環(huán)境條件 | |
環(huán)境溫度 | -15℃~55℃ |
工作電壓 | 不大于120%額定電壓 |
工作位置 | 任意 |
周圍磁場強度 | 小于0.5mT |
環(huán)境相對濕度 | 不大于90% |
大氣壓力 | 80~110KPa |
溫度 | -25℃~+70℃ |
海拔高度 | 不大于2500 米 |